How do you calculate phase to ground?

In a standard phase-to-phase connection, the variable that represents the grounding force is 1.73; it is divided from the voltage in order to compensate for the ground in a circuit. Using the same sample equation 12*5=60 volts, we can account for the ground by dividing 60 by 1.73, making the new voltage 34.68 volts.

How do you calculate per phase?

Divide the load by the voltage x route 3 x power factor. So 60000/ ( 440 x 1.732 x 0.8) = 98 . 41A per phase.

How do you calculate 3 phase to neutral voltage?

It is very easy, you only have to divide the Voltage Line to Line (Phase-Phase) between root of 3 (√3). Example: One Condenser air conditioner has a phase-phase voltage of 480V, to know the phase-neutral voltage of the condenser simply divide 480V between √3, being as follows: 480V / √3, resulting in 277V.

What is a 3 phase fault?

Three Phase Bolted Faults A three phase bolted fault describes the condition where the three conductors are physically held together with zero impedance between them, just as if they were bolted together. For a balanced symmetrical system, the fault current magnitude is balanced equally within the three phases.

How is 3 phase Watts calculated?

AC three phase amps to watts calculation formula

  1. P(W) = √3 × PF × I(A) × VL-L(V) So watts are equal to square root of 3 times power factor PF times amps times volts:
  2. watt = √3 × PF × amp × volt. or.
  3. W = √3 × PF × A × V. Example.
  4. P = √3 × 0.8 × 3A × 110V = 457W. Watts calculation with line to neutral voltage.

What is a 3 phase short circuit?

The most common type of short circuit in a three phase system is a single conductor to earth fault (Fig 1. Phase-to-earth). In all cases these faults are short circuits – the path of least resistance is through a fault, and not through the equipment you are attempting to power.